S-91-1.1 (2)i NO. GENERAL SEWER NOTES 1. THE SEWER SYSTEM SHALL CONFORM TO THE STANDARDS OF THE CITY OF COSTA MESA SANITARY DISTRICT. 2. CONTRACTOR SHALL REQUEST INSPECTION FROM THE OFFICE OF THE DISTRICT ENGINEER 48 HOURS PRIOR TO COMMENCEMENT OF WORK. TELEPHONE: (714) 631 -1731. 3. ANY WORK PERFORMED WITHOUT INSPECTION FROM THE DISTRICT SHALL BE CONSIDERED UNACCEPTABLE. 4. CONTRACTOR SHALL OBTAIN CMSD SEWER PERMIT PRIOR TO COMMENCEMENT OF WORK FROM THE DEPARTMENT OF STREETS AND SANITATION, CITY OF COSTA MESA, 77 FAIR DRIVE. TELEPHONE: (714) 754 -5323. 5. CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS THAT MAY BE REQUIRED BY THE LOCAL GOVERNING AGENCY. 6. CONTRACTOR TO HAVE A COPY OF APPROVED SEWER PLAN AND CMSD STANDARD PLANS AND SPECIFICATIONS ON JOB SITE AT ALL TIMES. 7. CLAY PIPE JOINTS SHALL BE TYPE "G" MECHANICAL COMPRESSION JOINTS FOR MAIN LINE SEWER. TYPE "D" JOINTS, BAND -SEAL OF APPROVED EQUAL, ARE APPROVED FOR LATERALS AND REPAIR WORK ONLY. 10. STAMP "S" ON CURB AT SEWER LATERAL LOCATIONS. M.C.W.D. STANDARD WATER CONSTRUCTION NOTES 1. ENGINEERING PLAN CHECK /INSPECTION FEE AND PERFORMANCE GUARANTEE BOND SHALL BE PAID AND APPLICATION /PERMIT (A.P.) COMPLETED BY THE APPLICANT PRIOR TO THE APPROVAL OF THE PLANS AND ISSUANCE OF THE A.P. FEES SHALL BE IN ACCORDANCE WITH DISTRICT RATES AND DEPOSIT SCHEDULE. 2. DEVELOPMENT IMPACT FEES SHALL BE COLLECTED BY THE DISTRICT AT THE TIME OTHER FEES ARE COLLECTED PRIOR TO APPROVAL OF PLANS OR SERVICE AGREEMENT, WHICHEVER IS FIRST. THIS FEE SHALL BE IN ACCORDANCE WITH DISTRICT RATES AND DEPOSIT SCHEDULE. 3. WATER MAINS WILL BE INSTALLED ACCORDING TO THE LATEST STANDARDS AND SPECIFICATIONS OF THE MCWD. 4. CONTRACTOR TO HAVE, ON THE JOB SITE, A COPY OF THE LATEST STANDARD SPECIFICATIONS AT ALL TIMES. 5. CONTRACTOR TO NOTIFY MCWD 48 HOURS PRIOR TO CONSTRUCTION (PHONE: 714/754 -5398 INSPECTION DEPARTMENT). 6. A PERFORMANCE GUARANTEE BOND SHALL BE HELD _ONE YEAR AFTER - MCWD'S NOTICE OF COMPLETION TO GUARANTEE WORK PERFORMED BY THE CONTRACTOR. 7. SEPARATION BETWEEN SANITARY SEWER AND WATER MAINS WILL BE 10' HORIZONTAL, 1' VERTICAL. 8. A 15' WATER MAIN EASEMENT WILL BE GRANTED TO THE MCWD FOR MAINTENANCE PURPOSES, 5' FOR WATER SERVICES (7.5' EACH SIDE OF MAIN; 2.5' EACH SIDE OF SERVICE). EASEMENT DOCUMENTS ARE TO BE SUBMITTED TO THE DISTRICT NO LATER THAN _30- DAYS AFTER NOTICE OF COMPLETION IS FILED. 9. SERVICE LATERALS WILL BE SET TO GRADE BY CONTRACTOR PRIOR TO THE INSTALLATION OF WATER METERS AND BOXES (PER MCWD'S STANDARD DRAWINGS #1, #2 AND #3). 10. WATER METER WILL NOT BE INSTALLED NOR WATER TURNED ON UNTIL THE BACKFLOW DEVICES REQUIRED FOR THE BUILDING AND IRRIGATION SYSTEMS HAVE BEEN INSTALLED, TESTED, APPROVED, AND CERTIFIED. CONTACT WATER QUALITY AT (714) 754 -5398. 11. PROTECT EXISTING UTILITIES IN PLACE. 12. WATER MAINS WILL HAVE 42" MINIMUM COVER TO FINISH GRADE. 13. RAISE EXISTING WATER VALVE COVERS TO GRADE (PER MCWD STANDARD DRAWING #14). 14. INSTALL FIRE HYDRANT PER MCWD STANDARD DRAWING #4. 15. INSTALL BLOW -OFF PER MCWD STANDARD DRAWING #9. 16. WATER MAINS WILL BE TESTED AT 225 P.S.I. FOR FOUR HOURS. 17. BACKFILL MATERIAL IN PIPE ZONE WILL HAVE A SAND EQUIVALENT OF 30 OR GREATER. REVISIONS i 7F zz a EXISTING 8" VCP SEWER TRIANGLE SQUARE SEWER &WATER PLANS CHIP OUT BASE OF EXISTING MANHOLE AND RECONSTRUCT NEW SMOOTH CHANNEL AS REQUIRED BY COSTA MESA SANITARY DISTRICT INSPECTOR. WORK REQUIRES BY -PASS OPERATION TO REMOVE SEWER FLOWS, OR AS OPTION, CONTRACTOR MAY PERFORM WORK IN EARLY MORNING HOURS IF FLOW IS LOW ENOUGH. 19TH STREET r- EXIST. 12" VCP SEWER OFF -SITE SEWER CONSTRUCTION 18. THE BACKFILL ABOVE THE PIPE ZONE WILL BE COMPACTED PER MCWD STANDARD DRAWING #18, AND BE IN COMPLIANCE WITH C.C.M. STANDARD DRAWING #813. 19. CHIP 2" "W IN CURB FACE TO IDENTIFY WATER SERVICE LOCATION. 20. INSTALL THRUST BLOCKS PER MCWD DISTRICT STANDARD DRAWING #12. 21. CONTRACTOR TO VERIFY DEPTH AND LOCATICN OF ALL UTILITIES PRIOR TO TRENCHING. 22. CONTRACTOR TO INSTALL TEMPORARY TAPS FOR TESTING AND CHLORINATION PRIOR TO CONNECTING TO EXISTING MAINS. 23. CONTRACTOR TO RETURN ALL MATERIAL REMOVED TO MCWD YARD, EXCEPT A.C.P., BROKEN CONCRETE, AND NATIVE SOIL. 24. WATER METERS AND BOXES TO BE INSTALLED BY MCWD BUT PAID FOR BY OTHERS. 25. A DOUBLE CHECK VALVE ASSEMBLY WILL BE REQUIRED ON ALL WATER METERED SERVICES TO ANY CONDOMINIUM UNIT OVER TWO STORIES OR FIVE OR MORE UNITS ON ONE METERED SERVICE. CONTACT WATER QUALITY AT (714) 754 -5398. 26. IRRIGATION METERS WILL REQUIRE A REDUCED PRESSURE PRINCIPLE ASSEMBLY. 27. A REDUCED PRESSURE PRINCIPLE ASSEMBLY WILL BE REQUIRED ON METERED WATER SERVICES TO ALL INDUSTRIAL BUILDINGS. 28. A DOUBLE CHECK VALVE ASSEMBLY WILL BE REQUIRED ON METERED WATER SERVICES TO ALL COMMERCIAL BUILDINGS. 29. IN LANDSCAPED AREAS, 0 TREES SHALL BE LOCATED IN MCWD EASEMENT OR WITHIN 7.5' OF ANY MCWD FACILITY. 30. FIRE LINES WILL NOT BE TURNED ON UNTIL THE DISTRICT ENGINEERING DEPARTMENT HAS RECEIVED A LETTER FROM THE OWNER OR HIS AUTHORIZED AGENT TO DO SO. THE LETTER WILL CONTAIN THE FILE NUMBER, JOB ADDRESS, SIZE OF DEVICE, AND ASSIGNED SERIAL NUMBER. CONTRACTOR WORK STARTED: WORK ACCEPTED: INSPECTED BY: DATE CONSTRUCTION NOTES & QUANTITIES: ITEM DESCRIPTION QUANTITY I UNIT SEWER CONSTRUCTION NOTES ONSITE OFFSITE n30. CONSTRUCT 6" VCP LATERAL PER C.M.S.D. STD. DWG. NO. S -104 -A 180 LF & S -104 -D LEGEND: 10 50. 31. CONSTRUCT 6" PVC LATERAL PER MODIFIED C.M.S.D. STD. T.C. TOP OF CURB ELEVATION DWG. NO. S- 104 -A. 1200 32. CONSTRUCT 6" CLEANOUT C.M.S.D. STD. DWG. NO. S -107. 16 33. REMOVE EXISTING UTILITIES. ALL EXISTING SEWER MH FRAMES & COVERS TO BE 51. RELOCATE EXISTING FIRE HYDRANT, (DRY BARREL PER DIST. STD. DWG. NO. 4. ) DELIVERED TO CITY CORPORATION YARD 2300 PLACENTIA AVE. 8 34. REPLACE CONCRETE PAVEMENT AND TRENCH PER CITY OF SF W5 COSTA MESA STD. DWGS. NO. 812 AND 813. EA WATER CONSTRUCTION NOTES ONSIT 41. INSTALL 2" WATER SERVICE ASSEMBLY PER M.C.W.D. STD. DWG. NO. 2. 53 42. INSTALL WATER METER PER M.C.W.D. STD. DWG. NO. 3 & 16. 2 PAD =XX.X (XX.XX) H.P. ( SIZE PER TABLE BELOW) 1 43. INSTALL 3 -2" WATER SERVICES IN COMMON TRENCH A 44. INSTALL 6" DOUBLE CHECK VALVE BACKFLOW PREVENTER PER INSTALL THRUST BLOCK PER DIST. STD. DWG. NO. 12. M.C.W.D. STD. DWG. NO. 17 W/ 5/8" BYPASS METER IN CUBIC FEET. xx.X 1r_R_L_ 145.1 LIZ INSTALL 6" PVC. PER M.C.W.D. STDS. (CLASS 150, AWWA, C900 WHITE). 725 46. INSTALL FIRE HYDRANT ASSEMBLY PER M.C.W.D. STD. DWG. NO. 4. 1 55. (WET BARREL) STD. 47. REPLACE CONCRETE PAVEMENT AND TRENCH PER CITY OF G.B. GRADE BREAK COSTA MESA STD. DWGS. NO. 812 AND 813. 148.1 INSTALL 6" RT. 45 DEGREE ELBOW WITH THRUST BLOCK PER 2 T.W. M.C.W.D. STD. DWG. NO. 12. 56. 49. INSTALL 6" RT. 90 DEGREE ELBOW WITH THRUST BLOCK PER 1 M.C.W.D. STD. DWG. NO. 12. TOP OF FOOTING INDICATES 2:1 SLOPE LEGEND: 10 50. INSTALL 16" X 6" HOT TAP WITH 6" R.W. VALVE PER M.C.W.D. STD. 10 T.C. TOP OF CURB ELEVATION 3 DWG. NO. 5 OR 6. W2 1 EA F.S. F.L. FINISHED SURFACE ELEVATION FLOW LINE ELEVATION 51. RELOCATE EXISTING FIRE HYDRANT, (DRY BARREL PER DIST. STD. DWG. NO. 4. ) 3 F.G. FF =XX.XX FINISH GROUND ELEVATION SHEET MATCH LINE TRACT BOUNDARY FINISHED FLOOR ELEVATION 1400 SF W5 II /2" EA 52. INSTALL CASING PER M.C.W.D. STD. DWG. NO. 10 OPEN CUT. MODIFIED FOR 125 53 INSTALL 1 -1/2" WATER METER PER M.C.W.D. STD. DWG. NO. 3 & 16. 2 PAD =XX.X (XX.XX) H.P. PAD ELEVATION EXISTING ELEVATION HIGH POINT ELEVATION 1 IRRIGATION SEE TABLE BELOW) MARKET A EA 54. INSTALL THRUST BLOCK PER DIST. STD. DWG. NO. 12. 1 1/2" 1 xx.X 1r_R_L_ DIRECTION OF FLOW EXISTING SPOT ELEVATION RIDGE LINE MALL 2 EA 1 55. RELOCATE EXISTING 2" AIR VAC PER M.C.W.D. STD. DWG. NO. 8. G.B. GRADE BREAK EXIST WATER METER T.W. TOP of WALL 56. ADJUST TO GRADE & PROTECT AS NEEDED. CITY ENGINEER R.C.E. T.F. ��- TOP OF FOOTING INDICATES 2:1 SLOPE 57. INSTALL 8" x 6" A.C. x FLG. 45' ELL W/ 6" R.W. VALVE. B S LF EA EA 520 I SF J =_• -L • BUILDINL, JtItlAGK LINt 1I )I INDICATES PRIVATE ONSITE WATER TABLE 10 EA FIXTURE UNITS 10 EA - 3 EA W2 1 EA EXISTING WATER EXISTING GAS O INDICATES PUBLIC OFFSITE WORK LF RESTURAUNT 3 EA SEWER 1400 SF W5 II /2" EA 79 FOOD COURT EA 125 2 EA 1I/2" 2 EA • �k 1 EA MARKET A EA 1 213 3 EA 1 1/2" 1 2 EA MALL 2 EA 1 EA J =_• -L • BUILDINL, JtItlAGK LINt 1I )I INDICATES PRIVATE ONSITE WATER TABLE REFERENCES BENCH MARK NO. REFERENCE PLANS ELEVATION NOTE TO CONTRACTOR DESCRIPTION STANDARD DRAWING N0. WATER METER DEMAND METER NO. SIZE FIXTURE UNITS GPM - -� - EXISTING SEWER 92 W2 - - - -- - -G-- 120.5 EXISTING WATER EXISTING GAS O INDICATES PUBLIC OFFSITE WORK I" RESTURAUNT 50 W4 SEWER 250 FOOD COURT W5 II /2" WATER 79 FOOD COURT o- WATER METER SEWER NOTES: 125 F FIRE HYDRANT 1I/2" CINEMA 92 • �k CLEAN OUT ELEVATION PER ARCHITECTS PLAN ALL NEW ON -SITE SEWER IS PRIVATE AND TO BE INSPECTED BY CITY OF COSTA MESA BUILDING DEPT. 754 -5290 MARKET POSSIBLE RESTURANT ® { ` 1 213 REMOVE AND REPLACE A.C. EXIST. STEEL POST EXIST. STREET LIGHT ALL NEW SEWER IN HARBOR BLVD. & 19TH STREET R/W TO BE INSPECTED BY THE COSTA MESA SANITARY DISTRICT (714) 631 -1731 1 1/2" 1 RESURANT MALL MALL EXIST. GAS METER ALL EXISTING SEWER TO BE REMOVED TO BE INSPECTED BY COSTA v„ x EXIST. EDISON VAULT EXIST. WATER VALVE EXIST. ELECTRIC VAULT MESA SANITARY DISTRICT (714) 631 -1731. CONTACT DISTRICT FOR ADDITIONAL INFORMATION ON EXISTING SEWER LATERAL LOCATIONS; THIS PLAN SHOWS EXISTING MAIN LINES ONLY. IRRIGATION NUMBER EXIST. TRAFFIC SIGNAL VAULT EXIST WATER METER DATE REFERENCES BENCH MARK NO. REFERENCE PLANS ELEVATION NOTE TO CONTRACTOR DESCRIPTION STANDARD DRAWING N0. WATER METER DEMAND METER NO. SIZE FIXTURE UNITS GPM W1 II/2" 210 92 W2 I" 120.5 50 W3 I" 120.5 50 W4 II /2" 250 98 W5 II /2" 125 79 W6 1" 125 45 W7 1I/2" 210 92 WS 1 II/2" 213 82.5 W9 1 11/2" 1 213 82.5 W10 1 1 1/2" 1 IRRIGATION 1 40 INFORMATION PROVIDED BY DOUBLE "0" ENGINEERING SEE PLUMBING PLANS FOR DETAIL EXIST. AIR VAC „COMMERCIAL DEVELOPMENT'S EXIST. TREE pFES�/ , r -- EXIST. GUYWIRE O �- JOB ADDRESS: 1850 NEWPORT BLVD. I" MESA CONSOLIDATED COSTA MESA L'i WATER DISTRICT ���GEK.t/KC SANITARY DISTRICT Ez�. �/ wwR • to { IoA G - -]W • (7Il) MI { ") MC -1117 Ma . uw PLAAMW wo SURVrnwo APPROVED FOR CONSTRUCTION WITHIN HARBOR BLVD. & 19TH STREET R/W ONLY NDER THE SUPERVISION OF: E �TDATE ND R. .E. 33292 DATE APPROVED BY DISTRICT ENGINEER DATE DESIGNED BY: DATE CHECKED BY: DATE TITLE SHEET DRAWN BY: CHECKED BY: SHEET TRIANGLE SQUARE 4 SEWER & WATER PLANS PLAN NUMBER DATE CITY OF COSTA MESA DEPARTMENT OF PUBLIC SERVICES / ENGINEERING DIVISION CITY ENGINEER R.C.E. AI it 1 07 1